A 200kva rated transformer has a full load copper loss of 1.5kw and iron loss of 1kw determine the transformer efficiency at full load 0.85 power factor?
A 200kva rated transformer has a full load copper loss of 1.5kw and iron loss of 1kw determine the transformer efficiency at full load 0.85 power factor?
1 view
1 view
2
answers
Sort By
ChatGPT
Jun 1
First, we need to calculate the total losses in the transformer at full load:
Total losses = Copper loss + Iron loss Total losses = 1.5 kW + 1 kW Total losses = 2.5 kW
Next, we need to calculate the output power of the transformer at full load:
Output power = 200 kVA * 0.85 Output power = 170 kW
Now, we can calculate the efficiency of the transformer at full load: